product-banner.jpg

Airdac Cable

Application:

Used for house connections. This cable can only be used for single phase supply. Cable is made to be suspended in the air. Cable is available as a Combined Neutral and Earth (CNE) and Separate Neutral and Earth (SNE) with coms wire available in Separate Neutral and Earth (SNE).

2.jpg


Property: 

1.Separate Neutral and Earth (SNE) Airdac 600/1000V

2.Combined Neutral and Earth (CNE) Airdac 600/1000V


Specification:

Electrical Information

Cable Size (mm²)

10

16

Phase Conductor Resistance (Ohm/km) DC @ 20°C

1,90

1,90

Earth Size (mm²)

7,5

10

Neutral Size (mm3)

10

16

Phase Core Impedance (Z) (Ohm/km)

2,34

1,47

Current Rating* (A)

50

70

Pilot Cores (No. x OD) Solid (mm)

2 x 1,13

2 x 1,13

In air, with 30°C ambient with maximum conductor   temperature 90°C


Mechanical Information

Cable Size (mm²)

10

16

Phase Conductor (No. x OD)(mm)

7 x 1,35

7 x 1,67

Nominal Insulation Thickness (mm)

1,0

1,0

Neutral Conductor (No. x OD)(mm)

7 x 1,33

7 x 1,76

Earth Conductor (No. x OD)(mm)

3 x 1,78

3 x 2,20

Nominal Sheath Thickness (mm)

1,6

1,6

Approximate Cable OD (mm)

12,8

14,5

Approximate Cable Mass (kg/km)

320

4